On-off controls are common on?

On-off controls are common on?




a. firetube boilers
b. watertube boilers
c. small package boilers
d. large package boilers
e. all of the above






Answer: C

If the damper motor does not operate on a boiler which one would NOT be the possible cause?

If the damper motor does not operate on a boiler which one would NOT be the possible cause?



a. Damper positioning switch in wrong position.
b. Linkage loose or jammed.
c. The lock-out switch has tripped.
d. Motor does not drive to "open" or "close" during prepurge or close on burner shutdown.
e. Motor does not operate on demand.





Answer: C

If the burner stays on low fire on a boiler which one would NOT be the possible cause?

If the burner stays on low fire on a boiler which one would NOT be the possible cause?



a. Boiler pressure above high-low fire control setting.
b. Damper positioning switch in wrong
c. Inoperative damper motor.
d. Flame detector weak or defective.
e. Defective high-low fire or modulating control.





Answer: D

If shutdown occurs during firing a boiler which one would NOT be the possible cause?

If shutdown occurs during firing a boiler which one would NOT be the possible cause?




a. Loss or stoppage of fuel
b. Defective fuel valve, loose electrical connections
c. Flame detector weak or defective
d. Lens dirty or sight tube obstructed
e. Boiler pressure above high-low fire control setting.






Answer: E

If a blower does not start which one would NOT be the possible cause?

If a blower does not start which one would NOT be the possible cause?




a. Main disconnect switch open.
b. Blown fuses, tripped overloads, loose electrical connections.
c. Damper positioning switch in wrong
d. Combustion control safety lock-out switch tripped.
e. Limit control circuit not completed.





Answer: C

On a boiler with high-low fire control, if the damper positioning switch is in the wrong position

On a boiler with high-low fire control, if the damper positioning switch is in the wrong position




a) the damper motor may not operate
b) a pre-purge will not occur
c) a high fire main flame ignition could occur
d) nothing will happen when the manual start switch is closed
e) the pre-purge period will last indefinitely unless the problem is corrected





Answer: A

The operating pressure control will control the

The operating pressure control will control the



a) steam pressure in the boiler
b) gas pressure to the burner
c) water pressure to the boiler
d) boiler furnace pressure
e) steam pressure in the steam header






Answer: A

The function of a programming control is

The function of a programming control is




a) to supervise feedwater supply to the boiler
b) to regulate the fuel supply to the burner
c) to regulate combustion controls during start-up
d) control the boiler blowdown rate
e) to regulate fuel, air, and water supply to the boiler





Answer: C

Automatic boiler programming controls

Automatic boiler programming controls



a) must incorporate a modulating control system
b) do not require interlocking devices
c) require an ON-OFF or two-position control switch
d) cannot make use of high-low fire control
e) are not interconnected with the water level control system





Answer: C

When an automatic unattended boiler starts up, the program timer will first:

When an automatic unattended boiler starts up, the program timer will first:



a. Energize the ignition transformer and pilot gas solenoid valve
b. Start the post purge period
c. Start the forced draft fan
d. Energize the main gas valve
e. Energize the main feed water valve





Answer: C

If a shutdown occurs during normal firing of a boiler and the steam pressure is below the normal cutout value, the problem could be:

If a shutdown occurs during normal firing of a boiler and the steam pressure is below the normal cutout value, the problem could be:



a. An interlock, such as the combustion air proving switch, has failed
b. Main flame trial failure
c. Pilot flame trial failure
d. Igniter transformer failure
e. High steam pressure limit switch tripped






Answer: A

An interrupted pilot of an automatic boiler:

An interrupted pilot of an automatic boiler:




a. Burns continuously, like that in a home furnace
b. Ignites before the main burner ignites, and is extinguished when the main burner is extinguished
c. Is one that has been extinguished by an inadequate flame signal
d. Ignites, is proven stable and extinguishes after the main flame is established
e. Must be manually ignited





Answer: D