Which of the following steps is not a step in the startup of a reciprocating or rotary compressor refrigerating system?

Which of the following steps is not a step in the startup of a reciprocating or rotary compressor refrigerating system?




a) Check oil level in the compressor, it should be at or above the centre of the sight glass.
b) Check the setting of high and low pressure cutout switches.
c) Open all shutoff valves in the system except bypass valves used elsewhere in the system.
d) Valves in lines connecting suction gages should be closed.
e) Check oil level in the compressor; it should be below the centre of the sight glass.







Answer: D

When a chiller has stopped due to low water temperature, and the chilled water temperature subsequently rises approximately 5-6°C above the chilled water temperature set point, the:

When a chiller has stopped due to low water temperature, and the chilled water temperature subsequently rises approximately 5-6°C above the chilled water temperature set point, the:





a. Compressor will restart
b. Compressor will require a manual reset
c. Cooling tower fan will restart
d. Cooling tower fan will shut down
e. Condenser pump will restart





Answer: A

To avoid liquid slugging in a direct expansion evaporator after shutting down a reciprocating or rotary compressor refrigerating system which of the following measures needs to be taken?

To avoid liquid slugging in a direct expansion evaporator after shutting down a reciprocating or rotary compressor refrigerating system which of the following measures needs to be taken?




a. Pump down the evaporator
b. Drain the liquid from the evaporator into the high-side
c. Discharge the condenser refrigerant into the evaporator
d. Open all the suction valves on the connecting condenser line
e. Fill the evaporator with refrigerant vapour







Answer: A

A system of regularly scheduled inspections and lubrications along with the adjustments, minor parts replacement and minor repairs necessary to keep the refrigerating plant and equipment in good operating condition is defined as what:

A system of regularly scheduled inspections and lubrications along with the adjustments, minor parts replacement and minor repairs necessary to keep the refrigerating plant and equipment in good operating condition is defined as what:




a. Preventive maintenance
b. Repair maintenance
c. Routing operation
d. Regular maintenance
e. Troubleshooting








Answer: A

Which of the following steps is not part of the start-up procedure of a centrifugal compressor refrigerating system?

Which of the following steps is not part of the start-up procedure of a centrifugal compressor refrigerating system?





a. Operate the oil pump for at least ten (10) minutes before starting the compressor
b. Open the stop valves in the chilled water system
c. Open the main circuit breakers
d. Open the makeup water valve
e. Check the refrigerant levels







Answer: C